NAVIGATION: Initial commissioning > Initial commissioning – Rotary system

Initial commissioning – Rotary system

Commissioning wizard

The wizard is used for targeted navigation through the subject areas relevant to initial commissioning. Setting the parameters correctly enables controlled movement of the drive by way of the manual mode window. For highly dynamic drive systems further settings must be made. If DriveManager 5 is opened with no project, a prompt appears asking if you want to carry out initial commissioning.


Hardware requirements

Prompt to perform initial commissioning

If this pop-up does not appear automatically, but you want to carry out commissioning using the wizard, you can also open the commissioning window again by clicking the pictogram or by way of the project tree. If the drive moves in an uncontrolled manner, or does not move at all, after initial commissioning, the parameter inputs must be checked.




Bild: Prompt to activate wizard


The wizard helps you with the initial configuration of the controller. Work through the individual subject areas in the specified sequence. Then the motor and controller will be set up.

Bild: Commissioning wizard



Subject area Action Instruction
Set the switching frequency and the voltage supply of the power stage. Adaptation of voltage supply to switching frequency
Decision whether to use a synchronous motor (PSM) or an asynchronous motor (ASM). Selection of motor
Decision whether to use a rotary or linear motion system. Selection of motor system

Identification

  • Measurement of:
    Stator resistance
    Rotor resistance
    Leakage inductance
  • Current controller tuning
  • Calculation of nominal flux
Identification of motor
  • Set the I2xt monitor
  • Select of temperature sensor
  • Characteristic setting
Motor protection
  • Encoder selection
  • Channel selection
Encoder setting
  • Motor phase test
  • Determine encoder offset
  • Determine mass inertia
Automatic tests

Open manual mode window

  • Control mode VFC (open loop)
  • Move motor at low speed
  • Check direction
Motor test in manual mode without intervention of a higher-level PLC
  • Optimize current controller
    (test signal generator) When there is a motor data set the current of the test signal generator is set automatically.
  • Optimize speed controller
  • Determine mass inertia [J] (basic settings)
  • Speed filter setting:
    P 0351 CON_SCALC_TF = (0,6 ms)
    Recommendation:
    SinCos encoder 0.2 ms - 0.6 ms
    Resolver 1 ms - 2 ms
  • Adapt control parameters to mechanism
    (adjust rigidity).

Controller setting

  • Current controller
  • Speed controller
  • Position controller
  • Units
  • Reference source
  • Reference processing
  • Stop ramps
  • Homing method
Motion profile setting

Limits:

  • Torque
  • Speed
  • Position
Define limits

Scaling, IOs, field buses:

  • CANopen
  • PROFIBUS
  • SERCOS

Set marginal conditions.

For more information refer to the user manuals for the individual bus systems.

Saving the settings:

Create a commissioning file

Saving: For more information on data handling refer to the Online Help in DriveManager 5

Tabelle: Commissioning wizard instructions